ACI 318-19 Footing Design Methodology

calcnote checks isolated and wall footings per ACI 318-19 Chapter 13: five design checks with all intermediate values exposed and a downloadable .docx calc-note. Run a footing calculation.

Bearing pressure (ACI 318-19 Sections 13.2.1, 13.2.2)

The footing must safely transfer the column load to the soil without exceeding its allowable bearing pressure. calcnote computes the factored net soil pressure from the column loads divided by footing area, minus the footing self-weight.

For eccentric or lateral loading, the resultant must land within the kern (middle third of the base) to keep the entire base in compression. Overturning and sliding stability are checked as service-level ratios.

Footing proportioning (sizing) uses service-level loads, while strength design of the footing section uses factored loads. calcnote separates these two stages: the engineer sizes the footing for allowable soil pressure, then the calculator checks the section for factored-load strength.

Read the full walkthrough: equations, worked example, and calculator →

Flexure at face of column or wall (Section 13.2.7.1)

The critical section for flexure is at the face of the column (isolated footing) or the face of the wall (wall footing). The factored upward soil pressure on the cantilevered overhang produces the design moment.

Minimum reinforcement per Section 13.3.3.2 referencing Table 24.4.3.2: As,min = 0.0018 · b · h for Grade 60 deformed bars, or 0.0020 · b · h for Grade 40/50 bars. The strength-reduction factor is φ = 0.90 (tension-controlled, Table 21.2.2).

Read the full walkthrough: equations, worked example, and calculator →

One-way (beam) shear (Sections 13.2.7.2, Table 22.5.5.1)

The critical section for one-way shear is at a distance d from the face of the column or wall. The concrete shear strength Vc is computed from Table 22.5.5.1 using the detailed ρw form (no shear reinforcement in typical footings).

The strength-reduction factor is φ = 0.75 (Table 21.2.1). The check compares the factored shear Vu at the critical section against φ · Vc.

Read the full walkthrough: equations, worked example, and calculator →

Two-way (punching) shear (Section 22.6.4.1, Table 22.6.5.2)

Punching shear is evaluated on a closed critical perimeter at d/2 from the face of the column or loaded area (Section 22.6.4.1), where d is the average effective depth of both reinforcement layers (Section 22.6.2.1).

Three vc equations from Table 22.6.5.2 govern: (a) the general two-way shear equation, (b) the column aspect-ratio (β) equation, and (c) the αs equation (interior, edge, or corner column). The smallest of the three controls.

This check applies to isolated footings only. Wall footings are exempt because the loaded area extends the full wall width (no closed perimeter forms).

Read the full walkthrough: equations, worked example, and calculator →

Development length (Sections 25.4.2.3, 25.4.2.4)

The bottom reinforcement must be developed within the available length: footing overhang minus cover. The required development length ld is computed per the governing clause 25.4.2.3 via the equation in 25.4.2.4a, with ψ factors from Table 25.4.2.5.

Minimum ld is 12 in. per Section 25.4.2.4. When As,provided exceeds As,required, the excess-reinforcement reduction applies. calcnote reports both the required and available development lengths and flags a warning when the bar cannot be fully developed.

Note: the engine's user-facing warnings cite "25.4.2.4a" (the specific equation); this hub cites both 25.4.2.3 and 25.4.2.4 (governing clause + equation section). Both are correct references at different granularity levels.

Read the full walkthrough: equations, worked example, and calculator →

Frequently asked questions

What design checks does ACI 318-19 require for isolated footings?

Bearing (13.2.1, 13.2.2), flexure at face (13.2.7.1), one-way shear at d from face (13.2.7.2, Table 22.5.5.1), punching shear at d/2 from column (22.6.4.1, Table 22.6.5.2), development length (25.4.2.3, 25.4.2.4), and service-level stability (overturning, sliding).

Where is the critical section for punching shear in a footing?

At d/2 from the face of the column or loaded area (ACI 318-19 Section 22.6.4.1), where d is the average effective depth of both reinforcement layers (22.6.2.1).

How does wall footing design differ from isolated footing design?

Wall footings are designed per unit length (1 ft strip). They have no punching shear check (the loaded area extends the full wall width, so no closed perimeter forms). Flexure and one-way shear are evaluated at the face of the wall and at d from the wall face, respectively. Minimum reinforcement follows Table 24.4.3.2.

What is the minimum reinforcement for a footing per ACI 318-19?

Per Section 13.3.3.2 referencing Table 24.4.3.2: 0.0018 · b · h for Grade 60 deformed bars, or 0.0020 · b · h for Grade 40/50 bars. This applies to both isolated and wall footings in each direction of reinforcement.