Punching shear in footings per ACI 318-19

Two-way (punching) shear is the tendency of the column to punch through the footing slab. ACI 318-19 evaluates it on a closed perimeter at d/2 from the column face (Section 22.6.4.1). Three concrete shear-strength equations from Table 22.6.5.2 apply; the smallest governs. This page covers punching shear for isolated footings under concentric loading. Eccentric moment transfer (γv / Jc per Section 8.4.4.2) is a separate analysis not covered here.

Applicable clauses

Clause Requirement
§22.6.4.1Critical section at d/2 from the face of the column or loaded area.
§22.6.2.1d = average effective depth of both reinforcement layers.
Table 22.6.5.2Three vc equations; the smallest governs (see below).
§22.6.5.3αs = 40 (interior), 30 (edge), 20 (corner).
§22.6.3.1√f'c capped at 100 psi for two-way shear.
§13.2.6.2λs = 1.0 for footings (size effect exemption).
Table 21.2.1φ = 0.75 for shear.

Critical section geometry

The critical section is a closed perimeter located d/2 from the face of the column, where d is the average effective depth:

$$d = \frac{d_1 + d_2}{2}$$

For a square interior column of side ccol, the critical perimeter and enclosed area are:

$$b_o = 4\,(c_{col} + d)$$
$$A_{crit} = (c_{col} + d)^2$$

For edge and corner columns the perimeter is truncated at the footing edge, and αs changes (see the lookup table below). calcnote handles all three column positions automatically.

The three vc equations (Table 22.6.5.2)

ACI 318-19 provides three concrete shear-strength equations. The governing value is the smallest of the three:

(a) General two-way shear:

$$v_{c,a} = 4\,\lambda_s\,\lambda\,\sqrt{f'_c}$$

(b) Column aspect ratio (β = long side / short side of column):

$$v_{c,b} = \left(2 + \frac{4}{\beta}\right)\lambda_s\,\lambda\,\sqrt{f'_c}$$

(c) Perimeter-to-depth ratio:

$$v_{c,c} = \left(2 + \frac{\alpha_s\,d}{b_o}\right)\lambda_s\,\lambda\,\sqrt{f'_c}$$

The governing capacity is:

$$v_c = \min(v_{c,a},\; v_{c,b},\; v_{c,c})$$

Equation (a) is the general cap. Equation (b) accounts for elongated columns where stress concentrates at the short sides. Equation (c) prevents the formula from becoming unconservative for very large perimeters relative to the slab depth. For square interior columns on typical footings, equation (a) almost always governs.

αs by column position

Column position αs When it applies
Interior40Column surrounded by footing on all four sides.
Edge30One face of column at or near the footing edge.
Corner20Two adjacent faces at or near the footing edge.

Footing-specific provisions

λs = 1.0 (Section 13.2.6.2): The size effect factor λs is taken as 1.0 for footings. This exemption recognizes that footing behavior under punching is better-constrained than flat slabs: the soil provides distributed upward reaction, and punching failure cracks in footings are steeper than in slabs.

√f'c cap (Section 22.6.3.1): For two-way shear, √f'c shall not exceed 100 psi. This limits the benefit of high-strength concrete in punching calculations. With f'c = 10,000 psi, √f'c = 100 psi exactly; concrete above 10,000 psi yields no additional punching capacity.

Computing Vu (demand)

The factored shear demand at the critical section equals the total factored column load minus the upward soil reaction acting within the critical perimeter:

$$V_u = P_u - q_u \cdot A_{crit}$$

The soil reaction inside the critical section pushes up against the punching cone, so it offloads the critical section. Omitting this deduction is conservative but can lead to unnecessarily thick footings.

Punching shear vs one-way shear

For typical isolated footings with centered square columns, punching shear is the more critical check. One-way shear tends to govern for long rectangular footings, large columns relative to the footing width, or wall footings (which have no punching check because the loaded area extends the full wall width and no closed perimeter forms). calcnote checks both automatically and reports the governing case.

Worked example: interior column

Input Value
f'c4,000 psi
λ1.0 (normal-weight)
Column16 × 16 in, interior
Footing7 ft × 7 ft × 20 in thick
Reinforcement#8 bars both ways, 3 in cover
Pu150 kips (concentric)

Step 1: Effective depth

Step 2: Critical perimeter

Step 3: Demand

Step 4: Capacity

Step 5: Check

For a square column, β = 1 makes equation (b) = 6√f'c, which never governs over (a) = 4√f'c. On typical footings (column dimension well under 4d), equation (a) also governs over (c). For very large columns on thin footings (ccol > 4d), equation (c) can drop below (a) and control. Rectangular columns with β > 2 are where equation (b) begins to control.

Frequently asked questions

What is the critical section for punching shear in a footing?

Per ACI 318-19 §22.6.4.1, the critical section is located at d/2 from the face of the column or loaded area, where d is the average effective depth of both reinforcement layers (§22.6.2.1). For a square interior column of side c on a footing, the critical perimeter is bo = 4(c + d).

How do you calculate punching shear demand Vu for a footing?

The factored shear demand at the critical section equals the total factored column load minus the upward soil reaction acting within the critical perimeter: Vu = Pu − qu × Acrit. For concentric loading, qu = Pu / (L × B) and Acrit is the area enclosed by the critical section (for example, (c + d)2 for a square interior column).

Does the ACI 318-19 size effect factor apply to footings?

No. Per §13.2.6.2, the size effect factor λs is taken as 1.0 for footings. This exemption recognizes that footing behavior under punching is better-constrained than flat slabs: the soil provides distributed upward reaction, and punching failure cracks in footings are steeper than in slabs.

When does punching shear govern over one-way shear in a footing?

For typical isolated footings with centered square columns, punching shear is the more critical check. One-way shear tends to govern for long rectangular footings, large columns relative to the footing width, or wall footings (which have no punching check because the loaded area extends the full wall width and no closed perimeter forms).