Footing bearing pressure check per ACI 318-19

Footing proportioning (sizing) is a service-level check: the footing must be large enough that the soil pressure under service loads does not exceed the net allowable bearing capacity. ACI 318-19 Sections 13.2.1 and 13.2.2 require that footings be proportioned for unfactored loads and net allowable soil pressure. This page covers the service-level proportioning checks: bearing, kern, overturning, and sliding. Strength design of the footing section (shear, flexure) uses factored loads and is covered on the hub page and other spokes.

Service loads vs factored loads

Footing design is a two-stage process. First, the footing is sized for service-level soil bearing: the base area is chosen so that the soil pressure under unfactored loads stays within the net allowable bearing capacity. Second, the footing section is checked for factored-load strength (shear, flexure, punching). ACI 318-19 §13.2.1 states: "Base area of footing shall be determined from unfactored forces and moments." The soil does not know about load factors; it responds to the actual (service) loads.

Applicable clauses

Clause Requirement
§13.2.1Footing base area determined from unfactored forces and moments.
§13.2.2Footing proportioned for net allowable soil pressure from geotechnical report.
§13.3.1.2Minimum footing depth 6 in above bottom reinforcement.

Net allowable bearing pressure

The net allowable pressure deducts the weight of the soil overburden and the footing self-weight from the gross allowable:

$$q_{net} = q_a - \gamma_{soil} \cdot D_f - \gamma_c \cdot \frac{h}{12}$$

The soil already supports its own weight and the footing weight before the column load arrives. Only the remaining capacity is available for the column load. ACI 318 does not specify qa; it comes from the geotechnical investigation (R13.2.2) or IBC Table 1806.2 for presumptive values.

Bearing pressure under service loads

For concentric loading (no moment):

$$q = \frac{P_{service}}{L \cdot B}$$

For eccentric or biaxial loading (resultant within kern):

$$q_{max} = \frac{P_{service}}{L \cdot B} + \frac{M_L}{S_L} + \frac{M_B}{S_B}$$
$$q_{min} = \frac{P_{service}}{L \cdot B} - \frac{M_L}{S_L} - \frac{M_B}{S_B}$$

Check: qmax ≤ qnet. When the maximum bearing pressure exceeds the net allowable, the footing is too small and must be resized.

Kern check (middle third)

The kern is the middle third of the footing base. For full-contact bearing (no uplift), the eccentricity of the resultant must stay within:

$$e_L = \frac{M_L}{P_{service}} \leq \frac{B}{6}$$
$$e_B = \frac{M_B}{P_{service}} \leq \frac{L}{6}$$

where eL and eB are eccentricities in inches. When the resultant falls outside the kern, part of the base lifts off and the effective bearing area shrinks. calcnote Phase 1 requires full-contact bearing; partial-contact analysis is not yet implemented.

Overturning stability

The footing must resist overturning about any edge:

$$FS_{ot} = \frac{M_{resist}}{M_{overturn}} \geq 1.5$$

Checked in each direction whenever the overturning moment in that direction is positive. A non-zero lateral shear V alone can trigger the check (V contributes to Moverturn through its lever arm h/12 even when Mservice = 0). The governing (lowest) factor of safety controls.

Sliding stability

The footing must resist horizontal sliding from lateral loads:

$$FS_{slide} = \frac{\mu \cdot P_{service}}{V} \geq 1.5$$

where μ is the soil-concrete friction coefficient (typically 0.3 to 0.5). Passive pressure on the footing sides is conservatively neglected.

Wall footings

Wall footings are analyzed per 1-ft strip: P is in kip/ft, M in kip-in/ft. The same bearing, kern, overturning, and sliding checks apply, with L = 1 ft implicitly.

Worked example: concentric isolated footing

Input Value
Pservice100 kips
qa4.0 ksf (from geotech report)
Soil unit weight120 pcf (0.120 kcf)
Depth below grade2.0 ft
Footing6 ft × 6 ft × 18 in thick
Moments / lateral loadNone

Step 1: Net allowable pressure

Step 2: Bearing pressure

Step 3: Check

In practice, the engineer sizes the footing so that q ≤ qnet. A 6×6 footing here uses 79% of the net capacity. If moments or lateral loads are present, eccentricity increases qmax and the kern, overturning, and sliding checks become active.

Frequently asked questions

What loads do you use for the footing bearing pressure check: service or factored?

Service loads. ACI 318-19 §13.2.1 requires that footing base area be determined from unfactored forces and moments. The soil does not know about load factors. Factored loads are used separately for the strength design of the footing section (shear, flexure).

What is the difference between gross and net allowable bearing pressure?

Gross allowable bearing pressure (qa) is the value from the geotechnical report or IBC Table 1806.2 for presumptive values. Net allowable pressure (qnet) deducts the weight of the soil overburden and the footing self-weight from qa, because the soil already supports those loads before the column load is applied.

What happens when the eccentricity exceeds L/6 in a footing?

When the eccentricity exceeds L/6, the resultant falls outside the kern (middle third). Part of the footing base lifts off, the effective bearing area shrinks, and the peak soil pressure increases sharply. calcnote Phase 1 requires full-contact bearing; partial-contact analysis is not yet implemented.

Does ACI 318-19 specify the allowable soil bearing capacity?

No. ACI 318 governs the concrete design of the footing section. The allowable soil bearing capacity (qa) comes from the geotechnical investigation (R13.2.2) or from IBC Table 1806.2 for presumptive values. The engineer must obtain qa from a separate source.