Footing flexural reinforcement per ACI 318-19
Footing flexure determines the bottom reinforcement in both directions. The footing overhang from the column face acts as a cantilever loaded by the upward soil pressure. ACI 318-19 Sections 13.2.7.1 and 13.3.3 govern. This page covers flexural design of the footing section using factored loads. Service-level proportioning is covered on the bearing pressure spoke. Development length of the reinforcement is covered in a separate spoke. This page applies to isolated footings and wall footings.
Critical section at the face
The critical section for footing flexure is at the face of the column or wall (Section 13.2.7.1(a)). The footing overhang beyond the column face acts as a cantilever: the upward soil pressure loads the overhang from below, producing a bending moment at the column face.
For shear, ACI moves the critical section to d from the face because loads within d of the support transfer directly through compression struts (arching action). Flexure has no such mechanism: the tension in the bottom steel must develop the full cantilever moment at the face. That is why the flexure critical section is at the face while the shear critical section is d (or d/2) away.
Applicable clauses
| Clause | Requirement |
|---|---|
| §13.2.7.1(a) | Critical section for moment at face of column or wall. |
| §13.3.3.2 | Minimum flexural reinforcement from Table 24.4.3.2. |
| Table 24.4.3.2 | As,min values by steel grade. |
| §13.3.3.3 | Reinforcement distribution in short direction of rectangular footings. |
| §25.2.1 | Minimum clear spacing between bars. |
| Table 21.2.2 | φ = 0.90 (tension-controlled). |
Factored moment (cantilever)
The factored upward soil pressure under concentric loading:
The cantilever arm from the column face to the footing edge:
The factored moment at the face:
where btrib is the tributary width perpendicular to the moment direction.
For isolated footings, two directions are checked:
- L-direction: moment about the L-axis, btrib = B (footing width), d = dbot (bottom layer)
- B-direction: moment about the B-axis, btrib = L (footing length), d = dtop (second layer, smaller effective depth)
For wall footings: single transverse direction per 1-ft strip, b = 12 in, d = dbot.
Minimum reinforcement (Table 24.4.3.2)
Section 13.3.3.2 requires minimum flexural reinforcement from Table 24.4.3.2:
| Steel grade | As,min |
|---|---|
| fy < 60 ksi (Grade 40/50) | 0.0020 · b · h |
| fy = 60 ksi (Grade 60) | 0.0018 · b · h |
| fy > 60 ksi (Grade 80+) | max(0.0018 · 60/fy, 0.0014) · b · h |
For typical footings with moderate loads, As,min almost always governs over the required flexural steel. This is because footings are sized for service-level bearing and the resulting section is conservatively thick for factored-load strength.
Reinforcement design (Whitney block)
The required steel area from moment demand, using the equivalent rectangular stress block:
where φ = 0.90 (tension-controlled, Table 21.2.2). Number of bars: n = ceil(As,design / Ab), minimum 2. Clear spacing per §25.2.1: sclear ≥ max(db, 1.0 in).
Two directions and effective depth
Isolated footings require reinforcement in both directions. The bottom layer (L-direction) uses dbot; the perpendicular layer on top of the first uses dtop, which has a smaller effective depth:
The L-direction (bottom layer) has a larger d and thus more capacity. For a square footing with a square column, both directions have the same moment but different capacities; the B-direction (smaller d) is the controlling direction.
Band width for rectangular footings (§13.3.3.3)
For rectangular footings where L ≠ B, the short-direction reinforcement is not uniformly distributed. A fraction γs of the total short-direction steel goes in a central band whose width equals the short side:
where β = long side / short side (≥ 1). The remaining (1 − γs) fraction is split equally between the two outer strips.
For a square footing, β = 1, γs = 1.0, and all steel is uniformly distributed (no band effect). calcnote computes and reports γs. Bar counts are currently for the full width; the band distribution is informational.
Wall footings
Wall footings are analyzed per 1-ft strip (b = 12 in). Only the transverse direction is designed for flexure: the cantilever from the wall face to the footing edge. The longitudinal direction carries shrinkage and temperature reinforcement only (not computed in the flexure check).
Worked example: concentric isolated footing
| Input | Value |
|---|---|
| Footing | 7 ft × 7 ft × 20 in thick |
| Column | 16 × 16 in, interior |
| Pu | 150 kips (factored, concentric) |
| f'c | 4,000 psi |
| fy | 60 ksi (Grade 60) |
| Reinforcement | #6 bars (db = 0.75 in, Ab = 0.44 in2), 3 in cover |
Step 1: Effective depth
- dbot = 20 − 3 − 0.75/2 = 16.625 in (L-direction)
- dtop = 20 − 3 − 3(0.75)/2 = 15.875 in (B-direction)
Step 2: Factored soil pressure
- qu = 150 / (7 × 7) = 3.061 ksf
Step 3: Cantilever arm
- ℓ = (84 − 16) / 2 = 34 in = 2.833 ft
Step 4: Factored moment (L-direction)
- Mu = 3.061 × 7.0 × 2.8332 / 2 = 86.0 kip-ft = 1,032 kip-in
Step 5: Minimum reinforcement
- As,min = 0.0018 × 84 × 20 = 3.024 in2
Step 6: Required reinforcement (Whitney block)
- discriminant = 16.6252 − 2 × 1,032 / (0.9 × 0.85 × 4 × 84) = 276.4 − 8.0 = 268.4
- a = 16.625 − √268.4 = 16.625 − 16.383 = 0.242 in
- As,req = 0.85 × 4 × 84 × 0.242 / 60 = 1.154 in2
- As,design = max(1.154, 3.024) = 3.024 in2 (minimum governs)
Step 7: Bar selection
- n = ceil(3.024 / 0.44) = 7 bars of #6
- As,provided = 7 × 0.44 = 3.08 in2
Step 8: Capacity check
- aprov = 3.08 × 60 / (0.85 × 4 × 84) = 0.647 in
- φMn = 0.9 × 3.08 × 60 × (16.625 − 0.647/2) = 2,711 kip-in
- DCR = 1,032 / 2,711 = 0.38 → OK
Minimum reinforcement governs, which is typical for footings. The required steel from moment demand (1.154 in2) is only 38% of As,min (3.024 in2). The B-direction has a smaller dtop but the same moment for a square footing; As,min still governs. For a square footing, γs = 2/(1+1) = 1.0 (uniform distribution).
Frequently asked questions
Why is the critical section for footing flexure at the face of the column, not at d away?
Unlike shear, there is no arching action to shift the critical section inward. The footing overhang acts as a pure cantilever: the upward soil pressure produces a bending moment that must be fully resisted at the column face. ACI 318-19 §13.2.7.1 places the critical section there.
How do you calculate minimum reinforcement for a footing?
From Table 24.4.3.2 via §13.3.3.2: As,min = 0.0018 · b · h for Grade 60 steel, 0.0020 · b · h for Grade 40 or 50, or max(0.0018 · 60/fy, 0.0014) · b · h for steel grades above 60 ksi. For typical footings, minimum reinforcement governs over the required flexural steel.
What is the band width rule for rectangular footings?
ACI 318-19 §13.3.3.3 requires that a fraction γs = 2 / (β + 1) of the short-direction reinforcement be placed in a central band whose width equals the short side of the footing. β is the ratio of the long side to the short side. The remaining steel is distributed equally in the two outer strips.
Does minimum reinforcement usually govern in footing design?
Yes. For typical footings with moderate loads, the required flexural steel from moment demand is well below As,min, so minimum reinforcement controls the design. This happens because footings are sized for service-level bearing capacity, and the resulting section is conservatively thick for factored-load strength.
Sources
- ACI 318-19: §13.2.7.1(a) (critical section at face), §13.3.3.2 (minimum reinforcement), Table 24.4.3.2 (As,min values), §13.3.3.3 (band width), §25.2.1 (clear spacing), Table 21.2.2 (φ = 0.90).