Column tie spacing requirements per ACI 318-19
Ties in a tied column restrain the longitudinal bars against buckling and confine the core. ACI 318-19 sets three families of rules: a maximum tie spacing (§25.7.2.1), a minimum tie size (§25.7.2.2), and bar-arrangement rules (§25.7.2.3). This page covers all three; calcnote's engine automatically checks the first two on every input.
The rules at a glance
| Clause | Requirement |
|---|---|
| §25.7.2.1 | Maximum vertical tie spacing smax = min(16·db,long, 48·db,tie, least column dimension). |
| §25.7.2.2 | Minimum tie bar size: #3 for longitudinal bars #10 and smaller; #4 for #11, #14, #18, and bundled bars. |
| §25.7.2.3 | Every corner and alternate bar supported by a tie corner (≤ 135° included angle); no unsupported bar > 6 in clear from a supported bar. |
| §10.7.6.2 | First tie within s/2 above the top of footing or slab and within s/2 below the lowest horizontal reinforcement in the slab, drop panel, or beam above. |
Verify tie spacing for your column: run a column check with a sample case, or view a demo.
Maximum spacing: the §25.7.2.1 envelope
Tie spacing along the column may not exceed the least of four limits:
- 16 longitudinal-bar diameters: restrains the vertical bars against buckling between ties.
- 48 tie-bar diameters: keeps the tie itself effective (a thin tie spaced far apart does little).
- The least section dimension (b or h; the diameter D for circular columns): a floor on confinement of the concrete core.
Lookup table: governing maxima by bar size
| Longitudinal bar | db (in) | 16·db (in) | Max with #3 ties (in) | Max with #4 ties (in) |
|---|---|---|---|---|
| #6 | 0.750 | 12.0 | 12.0 | 12.0 |
| #7 | 0.875 | 14.0 | 14.0 | 14.0 |
| #8 | 1.000 | 16.0 | 16.0 | 16.0 |
| #9 | 1.128 | 18.05 | 18.0* | 18.05 |
| #10 | 1.270 | 20.32 | 18.0* | 20.32 |
| #11 | 1.410 | 22.56 | not permitted (§25.7.2.2) | 22.56 |
48·dtie = 18.0 in for #3 ties, 24.0 in for #4 ties. The final limit is also capped by the least section dimension: a 12×20 column caps everything above at 12 in regardless of bars.
* Near-miss worth noticing: for #9 bars with #3 ties, 48·dtie = 18.00 in governs over 16·db = 18.05 in by five-hundredths of an inch, and for #10 bars with #3 ties the tie limit governs outright. Upsizing to #4 ties recovers the bar-based limit.
You don't need to carry this table to every check; calcnote validates §25.7.2.1 and §25.7.2.2 on every input and rejects violations with the governing limit named.
Minimum tie size: §25.7.2.2
#3 ties are permitted for longitudinal bars up to #10. #11 and larger longitudinal bars (and bundled bars) require at least #4 ties. That is why the #11/#3 cell above is struck: the combination is not a spacing problem but a tie-size violation.
Arrangement rules: §25.7.2.3
Spacing and size are necessary but not sufficient; rectilinear ties must also be arranged so that:
- Every corner bar and every alternate longitudinal bar has lateral support from the corner of a tie with an included angle of no more than 135°.
- No unsupported bar sits farther than 6 in clear along the tie from a laterally supported bar.
End-region placement rules (for example, locating the first tie within half a tie spacing above the top of a footing or slab) appear in §10.7.6.2. Scope note: calcnote checks the spacing envelope and minimum tie size; tie arrangement and end-region placement remain the designer's responsibility. Columns in special seismic systems follow the stricter hoop provisions of §18.7.5, which are outside calcnote's scope.
Frequently asked questions
What is the maximum tie spacing for a concrete column per ACI 318-19?
Per ACI 318-19 §25.7.2.1, column tie center-to-center spacing cannot exceed the least of 16 longitudinal bar diameters (16·db), 48 tie bar diameters (48·db,tie), or the least cross-sectional dimension of the column.
When are #4 ties required instead of #3 ties in a column?
Per ACI 318-19 §25.7.2.2, #3 ties are permitted for longitudinal bars #10 and smaller. Longitudinal bars #11, #14, and #18, as well as all bundled longitudinal bars, require at least #4 ties.
Which longitudinal bars require corner support from a tie?
Per ACI 318-19 §25.7.2.3, every corner bar and every alternate longitudinal bar must have lateral support provided by the corner of a tie with an included angle of no more than 135°, and no unsupported bar may be more than 6 inches clear along the tie from a laterally supported bar.
Sources
- ACI 318-19: §25.7.2.1 (spacing), §25.7.2.2 (minimum tie size), §25.7.2.3 (arrangement), §10.7.6.2 (end-region placement), §18.7.5 (seismic hoops, out of scope).