Sample result
Checked about X: depth h = 16 in
This is a live sample output for a 16×16 in rectangular tied column with 8-#9 longitudinal bars (f′c = 5,000 psi, Grade 60), checked per ACI 318-19 under Pu = 200 kip and M2 = 60 kip-ft. The same section is verified against StructurePoint's published spColumn reference; see the verification pages, the full report (PDF) and the methodology. Run your own column to get an editable .docx calc-note.
All 3 load cases pass (D/C ≤ 1.00). Governing: LC2 (D/C 0.80).
| Case | Pu (kip) | Mu (kip-ft) | D/C | Verdict |
|---|---|---|---|---|
| LC1 | 400.00 | 150.00 | 0.76 | PASS |
| LC2 (governs) | 600.00 | 100.00 | 0.80 | PASS |
| LC3 | 200.00 | 60.00 | 0.33 | PASS |
Compare lighter, heavier, and alternative reinforcement configurations side by side.
P-M interaction diagram
Demand (Pu, Mu) tested against the φ-reduced capacity envelope. Operating point (φPn, φMn) shown on the boundary. φ is computed per anchor from εt (§21.2.2); your operating point lies in the compression-controlled region; how the φ transition works.
Interaction Diagram Points ACI 22.4.2 (8 anchors, ACI 318-19 Table 22.4.2.1)
| Anchor | Description | c (in) | εt | φ | φPn (kip) | φMn (kip-ft) |
|---|---|---|---|---|---|---|
| 1 | Pure compression cap | N/A | N/A | 0.65 | 797.68 | 0.00 |
| 2 | Cap intersection | 17.35 | -0.00067 | 0.65 | 797.64 | 102.66 |
| 3 | Compression-controlled limit (εt = εty) | 7.99 | 0.00207 | 0.65 | 270.89 | 250.77 |
| 4 | Transition lower (εt = εty + 0.0015) | 6.17 | 0.00357 | 0.78 | 221.10 | 272.57 |
| 5 | Tension-controlled limit (εt = εty + 0.003) | 5.02 | 0.00507 | 0.90 | 171.64 | 286.75 |
| 6 | Tension-controlled deep (εt = εty + 0.008) | 3.10 | 0.01007 | 0.90 | -3.74 | 212.22 |
| 7 | Pure bending | 3.25 | 0.00946 | 0.90 | 0.00 | 213.93 |
| 8 | pure_tension | N/A | N/A | 0.90 | -432.00 | 0.00 |
| Quantity | Value |
|---|---|
| Pu (factored axial demand, kip) | 600.00 |
| φPn (axial capacity at operating point, kip) | 748.33 |
| Mu (= M2, design moment, kip-ft) | 100.00 |
No transverse load between supports. Cm from end-moment ratio per ACI 318-19 §6.6.4.5.3(a). |
|
| φMn (moment capacity, kip-ft) | 124.72 |
| c (neutral axis depth, in) | 16.05 |
| εt (extreme tension strain) | -0.00048 |
| φ (strength reduction factor) | 0.65 |
| φ regime (§21.2.2) | Compression-controlled φ = 0.65 throughout (εt ≤ εty = 0.00207) ACI Table 21.2.2 |
| D/C axial | 0.80 |
| D/C moment | 0.80 |
| kl/r about X | 25.00 |
Nonsway frames only (ACI 318-19 §6.6.4.3). The other axis (about Y) was not checked. kl/r about Y = 25.00, which exceeds the worst-case short-column limit of 22 (actual limit depends on the other-axis moments). Run the check about Y separately. Run about Y |
|
| kl/r limit | 28.00 |
| Tie spacing limit (§25.7.2.1) | 16.00 in (governed by b) |
| Bar clear spacing (§25.2.3) | 2.54 in ≥ 1.69 in |
Force Decomposition at Operating Point Per-bar detail (c = 16.05 in, a = 12.84 in)
| Component | Force (kip) | Moment (kip-in) |
|---|---|---|
| Cc (concrete compression) | 873.03 | 1,379.99 |
| Cs (steel in compression) | 278.26 | 922.58 |
| Ts (steel in tension) | 0.00 | 0.00 |
| Total = Pn, Mn | 1,151.28 | 2,302.57 |
| Layer | Bars | d (in) | εs | fs (ksi) | Force (kip) | Lever (in) | Moment (kip-in) |
|---|---|---|---|---|---|---|---|
| 1 | 4 | 2.50 | 0.00253 | 60.00 | 223.00 | 5.50 | 1,226.50 |
| 2 | 4 | 13.50 | 0.00048 | 13.81 | 55.26 | -5.50 | -303.92 |
| Section geometry | |
| Section | 16 × 16 in (rectangular) |
| Ag (gross area) * | 256.0 in² |
| Ast (total steel area) * | 8.00 in² |
| ρ (reinforcement ratio) * | 0.0312 (3.12%) |
| Materials | |
| f′c | 5,000 psi |
| fy (longitudinal) | 60 ksi (Grade 60) |
| Concrete | Normal weight |
| Reinforcement | |
| Longitudinal bars | 8-#9 |
| Per-face distribution | 2 per b-face, 0 per h-face (+ 4 corners) |
| Clear cover | 1.561 in |
| Transverse | #3 ties @ 12 in |
| Loads | |
| Pu | 600 kip |
| M2 (larger end moment) | 100 kip-ft |
| M1 (smaller end moment) | 50 kip-ft |
| Curvature | Single |
| Bending axis | X |
| Transverse load between supports | No |
| Slenderness parameters | |
| Lu (unsupported length) | 120 in (10.00 ft) |
| k (effective length factor) | 1 |
Assumptions and limits
- Tie arrangement and crossties (§25.7.2.3) are not checked.
Pro tier · in development
More capabilities are on the way as calcnote grows. Pricing under discussion; help shape it.
Download
Same calc note in either format.
Tell us what worked (or didn't)
calcnote is in active development. What would make this output more useful for your work? What's missing? What looked wrong? Short or long, we read every reply.
Verdict method 9 · build 5ee7a83 · generated 2026-11-24 04:18 UTC
This calculation was free, with no login required and no monthly caps. See how we compare